$ 522.22 Ex. GST
6 in stock (can be backordered)
The Zener barrier ZbC2+ is a certified intrinsically safe interface. It is used to connect a certified intrinsically safe device located in a potentially explosive atmosphere (Hazardous area) to a non-certified device that is in a safe area.
The Zener barrier prevents the transfer of unacceptably high energy from the safe area into the hazardous area.ย The ZbC2+ Zener barrier contains two identical diode return barriers in a common housingย and it is designed for DIN rail mounting in a safe area.
3 year warranty
MEASURED VALUE
Temperature
Relative humidity
BARRIER TYPE AND DESIGN
Two identical Zener barriers ZB1 and ZB2 in the common housing
Positive polarity with return diode
ELECTRICAL SPECIFICATION
Nominal resistance Roย 310 ฮฉ
Fuse ratingย 40 mA
Series resistanceย Rs1 = 355 ฮฉ (terminals 1-5, terminals 3-7)
Rs2 = 42 ฮฉ (terminals 2-6, terminals 4-8)
Voltage drop across return diodeย 0.8 V
Working voltage (SAFE terminals)ย max. 26 V at current of less than 10 uA
GENERAL TECHNICAL DATA
Operating temperature rangeย -20 to +60 ยฐC
Dimensionsย 22,5 x 114 x 100 mm
Weightย 125 g
Warrantyย 3 years
DATA FOR APPLICATION IN CONNECTION WITH HAZARDOUS AREAS
Directive conformityย 2014/34/EU
Compliance with standardsย EN IEC 60079-0:2018, EN 60079-11:2012
Certificateย FTZU 22 ATEX 0018X
Identification markingย EX ll (3)G [Ex ic Gc] IIC
Voltage Uoย 29,4 V
Current Ioย 96 mA
Resistance Roย min. 306 ฮฉ
Capacitance Co + Induktance Loย 120 nF + 2 mH or 60 nF + 4 mH
Maximum safe voltageย 250 V
Intrinsically safe humidity and temperature duct …
with Hazardous location certification (ATEX, IECE…
Intrinsically safe humidity and temperature trans…
Intrinsically safe humidity and temperature trans…
Reviews