Compressed-air ambient humidity, temperature Ethernet sensor with two relay outputs. T+RH probe from hard anodized duralumin for compressed air up to 25 bars with cable. Humidex reading.

Sensor H3531P is designed for online monitoring of temperature, relative humidity of air without aggressive substances. Three binary inputs to detection of two-states signals are the advantage. Other devices are controlled by two relay outputs.

High precision capacitive polymer sensor ensures excellent long term calibration stability and ultimate accuracy. Measured values are also converted to other humidity interpretation: dew point temperature, absolute humidity, specific humidity, mixing ratio and specific enthalpy.

The device is supplied with T+RH probe with 1m cable. Cable lengths 2m or 4m available optionally.

INCLUDED IN DELIVERY:

POWER SUPPLY IS NOT INCLUDED IN DELIVERY
3 year warranty

Specifications

MEASURED VALUE
Temperature
Relative humidity
Counted values (dew pointโ€ฆ)
Two-state signal

TEMPERATURE SENSOR
Measuring rangeย -30 to +105 ยฐC
Accuracyย ยฑ0.4 ยฐC
Resolutionย 0.1 ยฐC

HUMIDITY SENSOR
Measuring rangeย 0 to 100 % RH
Accuracyย ยฑ2.5 % RH from 5 to 95 % at 23 ยฐC
Resolutionย 0.1% RH

DEW POINT
Measuring rangeย -60 to +80 ยฐC
Accuracyย ยฑ1.5ยฐC for dew point temperature +10ยฐC and higher at ambient temperature +25ยฐC
ยฑ2.0ยฐC for dew point temperature 0ยฐC at ambient temperature +25ยฐC
ยฑ3.0ยฐC for dew point temperature -10ยฐC at ambient temperature +25ยฐC
ยฑ6.0ยฐC for dew point temperature -20ยฐC at ambient temperature +25ยฐC
Resolutionย 0.1 ยฐC

MEASURING THE MOISTURE OF COMPRESSED AIR
Measuring rangeย up to 25 bars
Air flow velocityย up to 25 m/s at a pressure of 1 bar (1m/s at a pressure of 25 bar)

RELAY OUTPUTS
Quantityย 2
Maximal voltageย 50 V
Maximal currentย 2 A
Maximal powerย 60 VA

BINARY INPUTS
Quantityย 3
Signal for binary inputyย dry contact, open collector or two-state voltage signal.
Inputs are not galvanically isolated.
Minimum pulse duration on binary inputย 500 ms
Voltage across open contactย < 3,3 V
Low voltage levelย 0 to +0,5 V
High voltage levelย +3,0 to +30 V

GENERAL TECHNICAL DATA
Operating temperatureย -30 to +80 ยฐC
Channelsย 1x connectable temperature+humidity probe
Acoustic alarmย from built-in beeper – switchable
Counted valuesย humidex, dew point, absolute humidity, specific humidity, mixing ratio, specific enthalpy
Outputย Ethernet
Measuring intervalย 2 s
Range of humidity sensor temperature compensationย all temperature range
Available temperature unitsย degrees Celsius, degrees Fahrenheit
Communication protocolย WWW, ModbusTCP, SNMPv1, SOAP, XML
Alarm protocolsย E-mail (SMTP authentication is supported), SNMP Trap, Syslog
Powerย 9-30 Vdc
Protection classย IP40
Dimensionsย 136 x 159 x 45 mm; length/diameter of external probe 150/18 mm
External probe cable lengthย 1 meter
Weightย approx. 410 g
Warrantyย 3 years