The complete solution for monitoring of temperature, humidity, pressure, CO2, voltage, current, pulses, events and other signals. Universal configurable inputs and outputs. For mounting to 19" rack - one rack unit 1U. Enables to build in the optional MP050 output relays module with 16 relays - see Optional accessories.
Data loggers are designed for measuring, recording, evaluation and subsequent processing of input electrical signals, which are subject to relatively slow changes (> 1s). In conjunction with the appropriate sensors and transducers are suitable for monitoring physical quantities.
The device includes traceable calibration certificate with declared metrological traceability of etalons is based on requirements of EN ISO / IEC 17025. The calibration sheet is always loaded as modules.
If the defined required configuration of inputs by, calibration certificate proves calibration inputs according to the required configuration - more than one range for each of the 16 inputs.
INCLUDED IN DELIVERY:
MEASURED VALUE
Temperature
Relative humidity
Counted values (dew point…)
Current
Voltage
Two-state signal
Frequency
Resistance
Event logging
GENERAL TECHNICAL DATA
Operating temperature 0 to +50 °C
Channels 1 to 16 inputs – software configurable
Memory 2MB (up to 480 000 values)
Memory type internal SRAM, backed-up by Lithium battery
Recording interval adjustable individually for all input channels from 1 second to 24 hours
Recording interval noncyclic – data logging stops after filling the memory
cyclic – after filling memory oldest data is overwritten by new
Real time clock year, leap year, month, day, hour, minute, second, backed-up by Lithium battery
Resolution of the AD converter (analog channels) 16 bits, conversion duration approximately 60ms/channel
Communication speed 9600, 19200, 57600, 115200 Bd, 230400* Bd (* pro USB, Ethernet)
Power 24 Vdc
Protection class IP20
Rozměry 483 x 190 x 44 mm – one rack unit 1U
Weight approx. 800 g
Warranty 3 years
Monitoring system MS may be configured for almost any desired measurement application. Sensors can be wired to datalogger in star-like connection as well as in serial. Combination of both is also possible. The monitoring system MS is characterized by a wide range of communication interfaces such as the RS232, RS485, USB, Ethernet and GSM or GPRS modem. Thanks to Wi-Fi routers several measuring systems MS can be wirelessly connected to a network.
The monitoring systems MS6xx is equipped with 16 freely programmable universal inputs. Each of them can be set to the input signal according to the table below. The monitoring system is thus very flexible and offers ease of use. The RS485 input must be ordered separately if you want to use the Modbus or Advantech communication interface.
Sixteen Channel Data Logger with Alarms
Sixteen Channel Data Logger with Alarms
Sixteen Channel Data Logger with Alarms
8-channel, data acquisition logger with 5″ touc…