The 4-20 mA current loop is the workhorse signal used to carry sensor readings in industrial sites. It sends a small current that represents temperature, humidity, pressure, level, flow etc., and remains reliable even over long cable runs. Because the signal starts at 4 mA, a drop to 0 mA often indicates a fault, making faults easier to spot. The loop also handles electrical noise better than many voltage signals, works with most PLCs and older controllers, and is widely supported across brands. This guide explains why 4-20 mA remains the industry standard.
What the 4-20 mA current loop is
A current loop is a simple circuit where a transmitter controls the current flowing through two wires.
A PLC, controller, or monitoring system reads the current and converts it into a real value you can use, such as bar, degrees, metres, or litres per minute.
In most setups:
- 4 mA is the lowest value in the sensor range
- 20 mA is the highest value in the sensor range
Values between 4 and 20 mA change linearly, making setup and checking easier.
Why the 4-20 mA current loop is important in industrial applications
1. Distinguishing zero and fault conditions
In a 4-20 mA loop, 4 mA represents the minimum or zero value, not 0 mA.
This matters because a really low reading still sends a valid signal. If the loop drops below 4 mA, especially to 0 mA, it usually points to a problem such as:
- broken wiring or loose connections
- power supply failure
- device malfunction
This helps teams quickly distinguish between a true reading and a system fault.
2. Predictable fault and out-of-range signalling
Many transmitters can also flag issues by moving outside the normal 4-20 mA band.
In practice:
- A reading below 4 mA may indicate an under-range or a fault.
- A current above 20 mA may indicate an over-range condition or a fault.
Some devices use set points like 3.6 mA and 21-22 mA, depending on settings. The key point is that unusual readings are easier to detect and alarm on.
3. Reliable over long cable runs
Long cable runs can cause issues for voltage signals because voltage can drop across the cable.
A current loop performs better over distance because the controller measures current. As long as the power supply provides sufficient voltage to drive the loop, the signal remains stable despite wiring resistance. This helps preserve accuracy when sensors are installed far from the control panel.
4. Better resistance to electrical noise
Industrial sites often have interference from motors, drives, welders, and switching equipment.
A current loop signal is usually less affected by this interference than low-level voltage signals. This helps reduce unstable readings, spikes, and false alarms in real operating conditions.
5. Works with legacy systems and modern PLCs
The 4-20 mA standard has been used for decades, so many older systems support it. Most modern PLCs and monitoring systems also accept it.
It integrates easily with:
- PLC analogue input cards
- controllers and indicators
- data loggers and recorders
This makes upgrades easier because you can often replace instruments without changing the whole control setup.
6. Standardisation across brands and easy replacement
Because 4-20 mA is widely used, devices from different manufacturers can usually work together without special converters.
This also makes maintenance easier. Replacement parts are easier to source, and technicians are more likely to know the wiring and testing methods already.
7. Loop-powered wiring reduces extra cabling
Many 4-20 mA transmitters are loop-powered, meaning the same two wires carry both the signal and power to the device.
This reduces the need for additional power cabling, shortens installation time, and lowers the risk of connection points failing. It is especially useful for remote instruments.
A practical note. Loop-powered devices have limited available power, so some instruments still need separate power. The loop-powered option is common, but not universal.
8. Linear output supports accurate control and reporting
4-20 mA signals are linear, which makes them easy to scale in a PLC and reliable for control decisions.
In most systems:
- 4 mA equals 0 per cent of the range
- 20 mA equals 100 per cent of the range
Example: If a sensor range is 0-10 bar:
- 4 mA equals 0 bar
- 12 mA equals 5 bar
- 20 mA equals 10 bar
This consistency helps ensure that logic, alarms, and reporting remain accurate.
9. Easy testing and calibration in the field
4-20 mA signals are linear, which makes them easy to scale in a PLC and reliable for control decisions.
In most systems:
- 4 mA equals 0 per cent of the range
- 20 mA equals 100 per cent of the range
Example: If a sensor range is 0-10 bar:
- 4 mA equals 0 bar
- 12 mA equals 5 bar
- 20 mA equals 10 bar
This consistency helps ensure that logic, alarms, and reporting remain accurate.
4-20 mA loops are simple to check with basic tools.
Technicians can measure loop current with a meter to confirm the signal is healthy. They can also use a loop calibrator to simulate 4 mA, 12 mA, and 20 mA during commissioning. This helps confirm wiring, PLC scaling, and alarm limits before the system goes live.
10. Works well with isolators and protection devices
Many industrial sites add isolators or barriers between field devices and control panels.
These devices help protect PLC inputs and reduce grounding-related issues, especially across large sites. 4-20 mA works well with these components, which support stable readings and safer installations.
11. Faster commissioning and easier long-term maintenance
Because 4-20 mA is widely understood, it supports faster setup, clearer documentation, and easier staff training.
It also suits staged upgrades, where you replace one device at a time without changing the whole signal method. This reduces risk and downtime throughout the plant’s life.
Key takeaways
The 4-20 mA current loop remains popular because it is reliable under real industrial conditions. It helps separate true readings from faults, stays stable over long cable runs, and handles electrical noise well. It also works with most PLCs and older control gear, supports simpler wiring with loop-powered devices, and is easy to scale, test, and maintain. For many industrial sites using modern industrial sensors and monitoring equipment, it remains one of the most practical ways to move sensor data from the field to the control room.
POPULAR PRODUCTS
-

COMET T5140 | 4-20mA CO2 Transmitter — Built-in Sensor
0 - 0 reviews$ 839.50 Ex. GST Add to cartCO2 concentration transmitter with 4-2…
-

COMET T3111 | 4-20mA Temperature & Humidity Transmitter
0 - 0 reviews$ 682.50 – $ 739.50Price range: $ 682.50 through $ 739.50 Ex. GST Select options This product has multiple variants. The options may be chosen on the product pageHumidity, temperature transmitter. Outdoor, indoo…
-

COMET T0110 | 4-20mA Temperature Transmitter
0 - 0 reviews$ 360.00 Ex. GST Add to cartTemperature transmitter with 4-20mA output
… -

COMET T3110 | 4-20mA Temperature & Humidity Sensor
0 - 0 reviews$ 635.00 Ex. GST Add to cartTemperature and humidity outdoor, indoor probe wi…
-

MadgeTech Process101A | 4-20mA Data Logger
0 - 0 reviews$ 586.61 Ex. GST Select options This product has multiple variants. The options may be chosen on the product pageCompact, low level DC current data logger, Availa…